Genset Controller >> Synchronising and Load Sharing

Trans-SYNCRO

Information

Auto Start Load Share Unit

Auto start load share unit, Automatic and manual start, Multi genset load sharing , Busbar voltages and frequency measurements, Dead bus sensing, Bus failure detection, Sequential set start, Manual voltage/frequeny adjustment, Equal aging of gensets, Direct/reverse governor and AVR control, Synchroscope, Programmable PLC functions
 

Specifications : 

Communication interface USB programming and communication port, CanBus communication with 1939 ECU, CanOpen, Ethernet, RS485
Inputs 13x Configurable digital, 4x Analogue senders, Magnetic Pickup, Charge Alternator D+(WL) inputs
Outputs Configurable 2x Relays, 7x Transistors, GBR outputs
Current Measurement 3 phases CT inputs for Load Current, 1x CT input for Earth Current
Voltage Measurement 3 phases for Alternator
Power Factor Measurement For 3 phases

 

Case : 

Dimensions 276mm x 189mm x 45mm
Panel Cut-Out 223mm x 162mm
Protection NEMA 4X IP65 at front side
Weight Approximately 0,53Kg

 

Ratings : 

DC Battery Supply range 8 to 32Vdc, max.operating current is 360mA
CT Secondary 5A
Sender Measurement 0 to 1300 ohm, accuracy: 1%FS, resolution: 1 ohm
Cabin. Temp. Measuremet -50 to +100 ºC, accuracy: 1 % FS, resolution: 1 ºC.
Operating / Storage Temp. -20°C to +70°C / -30°C to +80°C